Steam traps

Detailed display of steam trap

Steam Fittings

Steam traps

Steam traps are one of the most important fixtures in steam installations. Mistakes that can be made in steam trap selection and line design will cause the efficiency of the system to decrease and the fixtures to fail in a short time. In addition, steam leaks caused by steam traps bring a lot of financial burden to the businesses. Therefore, choosing the most suitable steam trap for the process is one of the biggest steps in energy saving. Accordingly, the line design should be made in a way that will not prevent the operation of the steam traps.

It is recommended to use a strainer before the steam traps and a check valve after them. It should not be forgotten that thanks to these fittings, the life of the steam traps will be extended and the system will work healthily.

An example of a trap connection diagram is shown below. In fact, the fixtures and order in which a trap should be installed are shown in the figure. It will be useful to design accordingly.

 

Steam trap drawing1-Ball Valve 2-Dirt Trap 3-Steam Trap 4-Check Valve 1-Ball Valve

The strainer here is used to hold the deposits formed by the condensation of steam in the condensate lines, while the check valve prevents the back pressure in the steam traps discharging in the same line and increases the discharge capacity. At the same time, it will prevent the backflow due to vacuum from damaging the steam traps.

Thermostatic Steam Trap DrawingThis type of steam trap is also known as encapsulated steam trap. Thermostatic steam traps can discharge condensate 10 to 30°C below the evaporation temperature. For example, since the evaporation temperature is 165°C in 6 bar processes, these steam traps discharge condensate below 135°C. Condensate above this temperature remains in the line and coils, forming a layer that prevents heating. The resistance of a 1 mm water film against heating is equal to the resistance of approximately 0.5 meters of copper. Therefore, especially in coil systems, water must be removed from the system as soon as it forms.

In addition, this water layer both prevents heat and causes water hammers, causing holes in connection fittings and even serpentines.

Inverted Bucket Steam Trap

Inverted Bucket Steam Trap DrawingThis type of steam trap, although it discharges the condensate as soon as it is formed, is insufficient to discharge the air. Since air is a much stronger insulator than water, air that cannot be discharged will delay heating considerably. The resistance of a 1 mm air film against heating is equal to the resistance of 13 meters of copper. In addition, since steam cannot enter the area where the air is located, the steam volume decreases. This also affects efficiency.

 

 

Float Steam Trap

Float Steam Trap DrawingThe float trap removes air from the system thanks to the air discharge element within it. With the help of the float, the condensate is removed from the process as soon as it is formed and the heating of the system is accelerated. The discharge temperature is at the steam temperature. Due to these features, the float trap is the most suitable type of steam trap in serpentine/plate heaters, air conditioning plants, dyeing machines and cylinder sanforizers.

 

Thermodynamic Steam Trap DrawingDue to its robust structure, it is preferred in main steam lines, line ends and collectors. In addition, it has high thermal efficiency as it discharges the condensate as soon as it is formed. Due to these features, this type of steam trap should be used in line ends and collectors. Discharge will be provided.

 

 

 

 